F114

FiWaGuard® Glass Bulb Actuator

The F114 uses a glass bulb as the temperature-sensitive element for local actuation.

Technical Data

response speed "fast" - RTI = 33(ms)1/2 / 59(fts)1/2
response temperatures 68°C, 79°C, 93°C (other options on request)
connection thread G1/8" (innen)
material stainless steel
options / special features mounting nut and optional protective cage